This guide outlines three common wiring setups for your MRCOOL Central Ducted Hyper Heat system, ensuring proper communication and functionality between the air handler, condenser, and thermostat.
1. Default 2-Wire Communication Setup
- Condenser to Air Handler: Connect to S1/S2 terminals. Tip: Make sure you are connecting to the proper terminals as there are 2 different plastic terminal covers, one of which is R/C.
- Air Handler to Thermostat: Use HA/HB terminals.
- This setup is specifically designed for the thermostat included with the MRCOOL kit.
This simple configuration ensures smooth operation.
2. 24V Thermostat Wiring Setup
- Condenser to Air Handler: Connect via S1/S2.
- Air Handler to Thermostat: Use 7 wires (R, B, C, G, Y1, Y2, W). W is only needed if using heat strips. Y1 or Y2 will not be needed if you do not need to stage the system.
- Settings: Adjust dip switches (SW1-1) to on at the air handler. Set the thermostat as a staged heat pump or non staged based on your wiring. Also, set the reversing valve to energize in heat mode as the default is cooling mode.
- Terminal Designations for 7-Wire Setup:
- R: 24V power
- B: Reversing valve (heat active)
- C: Common
- G: Indoor blower motor
- Y1: 1st stage compressor
- Y2/Y: 2nd stage compressor
- W: Auxiliary heat
This configuration provides the most flexibility.
3. Full 24V Wiring Setup
- Thermostat to Air Handler: 7-wire setup (same as Scenario 2).
- Air Handler to Condenser: Use 24V terminals instead of S1/S2.
- Settings: Set dip switches (SW1-1, SW1-4) to on at the air handler, and dip switch 2 to on at the condenser.
This configuration provides the most control over operation.
Conclusion
Choose a setup based on your thermostat preference. Ensure proper terminal connections and dip switch settings for optimal performance. If unsure, consult a professional.
Related to
Comments
0 comments
Please sign in to leave a comment.